PUC Distributions supplying voltages at the service entrance to customers in accordance with PUC's condition of service and CSA Standard Voltage Requirements CAN3-C235 are:

Recommended Voltage Variation Limits of Circuits up to 1000 V, at Service Entrances

 

NOMINAL SYSTEM VOLTAGES (V)

NORMAL OPERATING CONDITIONS

EXTREME OPERATING CONDITIONS

Min (V)

Max (V)

Min (V)

Max (V)

SINGLE PHASE

120/240

110/220

125/250

106/212

127/254

600

550

625

530

635

THREE PHASE, 4-WIRE (WYE)

120/208

112/194

125/216

110/190

127/220

347/600

318/550

360/625

306/530

367/635

THREE PHASE, 3-WIRE

240

220

250

212

254

600

550

625

530

635

If you believe you are experiencing power quality concerns, please contact our Customer Experience team at 705-759-6500 and they will schedule you an appointment for a PUC employee to inspect the equipment leading to your home. 